ABB | SACE Emax 2
Electronic accessories | 7 - Ekip Com Profibus modules
199 | © 2013 ABB | 1SDH001000R0002 - L7804
Connections
The modules must be mounted on the terminal box of the circuit-breaker or of the fixed part of
the withdrawable circuit-breaker, in the first free slot after the Ekip Supply module.
Information on the assembly is available from the web site http://www.abb.com/abblibrary/
DownloadCenter/, in particular with the kit sheet 1SDH001000R0512.
The wiring diagrams for the modules are included below:
YO
01
H4
02
K5
04
K10K9
94
92
H3
9181
H2
82
K4
K8
8474
K7
K3
H1
72
7161
HC
62
64
54
52
51
EKIP SupplyModuleTrip Unit I/O
HC
K6
Ge-
Ge
Szc
K2
K1
W4
W3
R2
R1
Q4Q3Q2Q1YC2YC
YU
YO2
RTC
I/O
TU
44
42
41
34
32
31
24
22
21
14
12
11
C22
C21
C12
C13
C11
C2
C3
C1
D2
D1
48
46
45
Ne
Rca
Ne-
Gzi
Szo
Szi
Gzo
Rct
Vn
V1
V2
V3
U2
U1
38
36
35
98
96
95
YRMS33S51
EKIP Signalling 4KQ5..Q10
Module Module
HC
XV
A4
X
X
XV
A3
A4
53
W5
W5 W6
(B)(A)
W5 W6
W6
194
XK7 XK7
1 2
193
S75I/5
BUS 1
Ekip Com Profibus
COM
K51
O)
*
* L), *M)*L), *M)
Ekip Com R Profibus
BUS 2
W6R
W6RW5R
(A) (B)
W6RW5R
W5R
63
K51
COM
Diagrams 53 - 63
Further information is available on page 156, or on the site http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
Termination resistors
The modules provide the possibility to insert a 220 Ω termination resistor on the RS-485 bus,
by setting the dip-switches Rterm on the side of the modules, in position on.
In the event of termination of the bus, a 390 Ω pull-up or pull-down resistor must also be
inserted on the lines, by setting the dip-switches Rpoll, in position on.
These options must be selected before installation of the modules.
For the positions on and off of the dip-switches, see the following figure.
Figure 89
Access from the display
With the modules powered, and Local Bus enabled, the presence of the modules on the
terminal box activates additional menus on the display, to configure the modules according to
the characteristics of the network.
To enable the Local Bus, you need to select "On" in the menu Settings, Modules, Local Bus.
The following table illustrates the path for accessing the configuration parameters of the
modules from the display:
Settings
…
Network frequency
Modules
Local/Remote
Local Bus
…
Ekip Com Profibus Serial address
Ekip Com Profibus *R Serial address
…
Function
Power Controller
…
NOTE: the modules can also be configured with the Ekip Connect application (see
the chapter “13 - Other accessories", and the paragraph "Ekip Connect application"
on page 221).
The default serial address is 2 for the Ekip Com Profibus, and 3 for the Ekip Com Profibus
Redundant, and can be modified with a value between 1 and 125.
IMPORTANT: devices connected to the same network must have different
addresses.
The following table illustrates the path from the display for accessing information on the
modules:
Information
Protection unit
Circuit-breaker
Modules
…
Ekip Com Profibus
Ekip Com Profibus *R
…
Power Controller
The information on the modules that can be viewed includes the serial number and the software
version.