EasyManuals Logo

ABB SACE Emax 2 Series Installation, Operation And Maintenance Instructions

ABB SACE Emax 2 Series
271 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #114 background imageLoading...
Page #114 background image
ABB | SACE Emax 2
110 | © 2013 ABB | 1SDH001000R0002 - L7804
Ekip Touch protection release | 11 - Hi-Touch protections
Summary table of Hi-Touch protections
ABB
ANSI
(4)
Threshold
Tolerance
threshold
Time
Calculation
formula t
t
(1)
Tolerance t
t
(2)
S2 50 TD
I5 = 0.6...10 In
Step = 0.1 In
± 7 % I5 6 In
± 10 % I5 > 6 In
t5 = 0.05...0.8 s
step = 0.01 s
t
t
= t5
The better of the two
values:
± 10% or ± 40 ms
D 67
I7 = 0.6...10 In
Step = 0.1 In
± 7 % I7 6 In
± 10 % I7 > 6 In
t7 = 0.2...0.8 s
step = 0.01 s
t
t
= t7
The better of the two
values:
± 10% or ± 40 ms
UV2 27
U15= 0.5….0.98 Un
Step = 0.001 Un
± 5 %
t15 = 0.05…60 s
step = 0.05 s
t
t
= t15
The better of the two
values:
± 10% or ± 40 ms
OV2 59
U16= 1.02….1.5 Un
Step = 0.001 Un
± 5 %
t16 = 0.05…60 s
step = 0.05 s
t
t
= t16
The better of the two
values:
± 10% or ± 40 ms
UF2 81L
f17= 0.9….0.99 fn
Step = 0.01 fn
± 5 %
t17 = 0.2…60 s
step = 0.1 s
t
t
= t17
The better of the two
values:
± 10% or ± 40 ms
OF2 81H
f18= 1.01….1.1 fn
Step = 0.01 fn
± 5 %
t18 = 0.5…60 s
step = 0.01 s
t
t
= t18
The better of the two
values:
± 10% or ± 40 ms
Table of Additional Functions of the protections
The following table summarises the additional functions combined with protections S2 and D:
ABB Threshold
Threshold tolerance
(2)
Time
(3)
Calculation
formula t
t
(1)
Tolerance t
t
(2)
S2
(Startup)
I5
startup
= 0.6...10 In
step = 0.1 In
± 7 % with I5 6 In
± 10 % with I5 > 6 In
t5
startup
= 0.1…30 s
step = 0.01 s
t
t
= t5
startup
The better of the two values:
± 10 % or ± 40 ms
D
(Startup)
I7
startup
= 0.6...10 In
step = 0.1 In
± 10 %
t7
startup
= 0.1…30 s
step = 0.01 s
t
t
= t7
startup
The better of the two values:
± 10 % or ± 40 ms
D
(SdZ)
- -
t7
SdZ
= 0.13…0.5 s
step = 0.01 s
- -
(1)
The calculation of t
t
is valid for values that have exceeded the activation threshold of the protection.
(2)
Valid tolerances with release energized in service conditions or with the auxiliary, tripping time = 100 ms, temperature and currents within operating
limits. If the conditions are not guaranteed, the tolerance of the tripping time becomes ± 20%.
(3)
For the startup functions, the specified time is the period for which the protection with the different threshold remains active, calculated from when
the startup threshold is exceeded.
(4)
ANSI / IEEE C37-2 encoding.

Table of Contents

Other manuals for ABB SACE Emax 2 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB SACE Emax 2 Series and is the answer not in the manual?

ABB SACE Emax 2 Series Specifications

General IconGeneral
Breaking capacityUp to 150kA
Number of poles3 or 4 poles
Communication protocolsModbus, Profibus
StandardsIEC 60947-2
TypeAir circuit breaker
MountingFixed, Withdrawable

Related product manuals