20 - Default parameters
Ekip TOUCH default parameters
The Ekip Touch releases are supplied with the following default parameters:
Protection/Parameter
Value
(1)
L 1 In; 144 s; Prealarm: 90 %
S
(2)
Off; 2 In; 50 ms; Curve: t = k
I 4 In
MCR Off; 6 In; 40 ms
G
(2)
Off; 0.25 In; 400 ms; Curve: t = k
IU Off; 50%; 5 s
OT Off
Current thresholds Off; 1: 50 %; 2: 75 %
Current thresholds Off; Iw1: 3 In; Iw2: 3 In
Harmonic Distortion On
Gext
(2) (3)
Off; 0.25 In; 400 ms; Curve: t = k
Rc
(3)
Off; 3 A; 60 ms
Frequency 50 Hz
Neutral
Off (for CB 3 P)
50% (for CB 4 P)
Datalogger Off
Power Controller see note
(4)
Hardware Trip Disabled
Monitor Time 5 min
Local bus Disabled
Alive LED Disabled
Language English
Password 00001
Mode Local
Modbus RTU par Address: 247; baudrate: 19.2 Kb
Profibus par Address: 2
Devicenet MAC ID: 63; baudrate: 125 Kb
Modbus TCP Static IP: 0.0.0.0
(1)
Thermal memory, startup, Zone selectivity set to Off.
(2)
Protection S available with LSI and LSIG versions of the release. Protection G available with LSIG version.
(3)
Protections available in the presence of the respective sensors.
(4)
Protection activated on request when purchasing the release.
The protections activated by the presence of the Ekip Measuring Pro module, have the following
default parameters:
Protection/Parameter Value
VU Off; 50%; 5 s
UV Off; 0.9 Un; 5 s
OV Off; 1.05 Un; 5 s
UF Off; 0.9 fn; 3 s
OF Off; 1.1 fn; 3 s
RP Off; 0.1 Sn; 10 s
Phase Sequence 123
Cos φ Off; 0.95