ABB | SACE Emax 2
Emax E2.2-E4.2-E6.2 circuit-breakers | 6 - Installation
27 | © 2013 ABB | 1SDH001000R0002 - L7804
Connection to the power circuit
The connection of a circuit-breaker to the power circuit is performed using the connection
busbars of the electric switchgear fixed to the terminals of the circuit-breaker. The sizing of the
busbars is specified by the designer of the electrical switchgear.
Figure 58
IMPORTANT: it is possible to obtain
different capacities for the
connections by altering the
thickness and number of busbars
in parallel.
The following table provides some examples of the amount and sizes of the connections that
can be used for each type of circuit-breaker:
Circuit-breaker Iu (A)
Dimension of
busbars
Horizontal
terminals
Vertical
terminals
E2.2 N S H 800 1x50x10 yes yes
E2.2 N S H 1000 2x50x5 yes yes
E2.2 N S H 1250 2x50x10 yes yes
E2.2 B N S H 1600
2x60x10 yes -
1x100x10 - yes
E2.2 B N S H 2000
3x60x10 yes -
2x80x10 - yes
3x60x10* yes -
2x80x10* - yes
E2.2 N S H 2500
3x60x10 yes -
4x100x5 - yes
3x60x10* yes -
4x100x5* - yes
E4.2 V 2000 2x80x10 yes yes
E4.2 V 2500 2x100x10 yes yes
E4.2 N S H V 3200 3x100x10 yes yes
E4.2 N S H V 4000 4x100x10 yes yes
E6.2 H V X 4000 4x100x10 yes yes
E6.2 H V X 5000 5x100x10 yes yes
E6.2 H V X 6300 7x100x10 yes yes
(*): values for spread terminals
Continued on the next page