EasyManua.ls Logo

ABB SACE Emax 2 Series - YU: Under-Voltage Coil

ABB SACE Emax 2 Series
271 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB | SACE Emax 2
Electrical accessories | 1 - Electrical Control accessories
227 | © 2013 ABB | 1SDH001000R0002 - L7804
YU: under-voltage coil
YU
YO2
D2
D1
The under-voltage coil YU controls the value of the voltage in the circuit to which it is connected.
The coil opens the circuit-breaker when:
the power supply voltage of the coil drops to a value in the range 35%… 70% Un
The under-voltage coil YU can in addition be used for the following purposes:
Release the circuit-breaker remotely using push-buttons of the normally closed type.
Activate the lock when the circuit-breaker is closed (the closing of the circuit-breaker is
allowed only with the under-voltage coil energized).
NOTE: The power supply of the coil must drawn on the supply side of the circuit-
breaker or from an independent source.
The tables listing the available voltages and the electrical characteristics are provided below:
Available voltages (Un)
24V AC/DC
30V AC/DC
48V AC/DC
60V AC/DC
110V…120V AC/DC
220V…240V AC/DC
240V...250V AC/DC
380V…400V AC
415V…440V AC
480V…500V AC
General characteristics YU
Operating limits (Standards
IEC60947-2)
85%...110% Un
Inrush power (Ps) AC= 300VA DC= 300W
Continuous power (Pc) AC= 3.5VA DC= 3.5W
Opening time 50ms
YU: Connections
Further information is available on page 156, or on the site http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
A4
X
XV
X
XV
A1
A4
73
D1
D1
D1
YU
D2
D2
D2
-
~
~
+
SO
XB5
1
XB5 2
Diagram 73
Information on the assembly is available from the web site http://www.abb.com/abblibrary/
DownloadCenter/, in particular with the kit sheet 1SDH001000R0504.