EasyManua.ls Logo

ABB SACE Emax 2 Series - 5 - IPS Interface protections

ABB SACE Emax 2 Series
271 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB | SACE Emax 2
Ekip Touch protection release | 17 - Test
141 | © 2013 ABB | 1SDH001000R0002 - L7804
17 - Test
Test
Path
Main page - Menus - Test
Presentation
All the releases of the Ekip Touch range allow you to carry out various checks directly from the
display:
Self-test, for the check on the display and the LEDs.
Trip Test, for the check on the circuit breaker opening command.
Test CB, for the check on the controls of the circuit-breaker opening and closing coils
Zone Selectivity, for the check on inputs and outputs of zone selectivity.
In the presence of auxiliary power supply and contact type modules, the dedicated sections
are enabled:
Ekip Signalling 4K, it allows the check of LED and contacts of the module.
Ekip Signalling 2K-1, 2K-2, 2K-3, it allows the check of LED and contacts of the module.
Ekip Signalling 10K-1, 10K-2, 10K-3, it allows the check of LED and contacts of the
module.
In the presence of an Rc type release and auxiliary power supply, the dedicated test section
is enabled:
RC test, allows you to check the connection and correct operation of the residual current
sensor.
NOTE: access to the test menu requires the insertion of the password.
Using the test accessories Ekip T&P and Ekip Bluetooth it is also possible to verify the
commands of the protections.
Self-test
The automatic sequence of the display and the LED is activated by selecting the command
Self-test.
The sequence includes the following test phases:
Phase Operation
1 Screen with message “www.abb.com”.
2 Darkening of the display.
3
Color sequence with red, green, blue bands, with gradual increase of
backlighting
4 Warning and Alarm LEDs switched on for 1 second.
Trip Test
Selecting the command Trip test opens a dedicated page that requests confirmation for
performing the test by pressing the iTest key.
When the key is pressed, an opening command is sent to the trip coil.
IMPORTANT: the trip command is performed with the circuit-breaker closed
and absence of circulating currents.
Continued on the next page