EasyManua.ls Logo

ABB SACE Emax 2 Series - Access from the Display

ABB SACE Emax 2 Series
271 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB | SACE Emax 2
180 | © 2013 ABB | 1SDH001000R0002 - L7804
Electronic accessories | 4 - Ekip Signalling 4K module
Access from the display
To configure the module the release must be on. Then the presence of the module activates
the additional menus on the display:
In order to configure the inputs and output contacts.
To display information on the module and the state of inputs and outputs.
The following table illustrates the path for accessing the configuration parameters of the
module from the display:
Settings
Network frequency
Modules
Local/Remote
Local Bus
Ekip Signalling 4K
I 01
Polarity
Delay
I 02
(1)
I 03
(1)
I 04
(1)
O 01
Signal source
Delay
Contact Type
Self-latching
min Activation Time
O 02
(2)
O 03
(2)
O 04
(2)
Function
Power Controller
(1)
Like the menu I 01.
(2)
Like the menu O 01.
NOTE: the module can also be configured the Ekip Connect application (see the
chapter "13 - Other accessories", and the paragraph "Ekip Connect application" on
page 221).
The following table illustrates configuration parameters of the inputs:
Parameter Selectable values Default Description
Polarity
Active open, Active
closed
Active
closed
• Active open = To be considered
active, the input must be floating.
• Active closed = To be considered
active, the input must be connected
to its reference.
Delay
00…100.00 s
in steps of 0.01 s
0.01 s
Standby time after that the input
has changed state, before the
change of state is recognised (if the
input is reset before a time equal to
the delay has elapsed, the change
of state is nor recognised). If 0.00
s is selected, the value 300 μs is
assigned to the parameter.
Continued on the next page

Table of Contents

Other manuals for ABB SACE Emax 2 Series

Related product manuals