ABB | SACE Emax 2
Ekip Touch protection release | 9 - Touch protections
91 | © 2013 ABB | 1SDH001000R0002 - L7804
Current thresholds
Path
Main page - Menu - Advanced protections
Function
The Current Thresholds allow controls to be set on the current lines, to be connected to the
programmable contacts of the Ekip Signalling modules (in all versions). 2 pairs of contacts are
available:
Threshold 1 and Threshold 2, with control referring to I1.
Threshold Iw1 and Threshold Iw2, with control referring to In.
IMPORTANT:
The current thresholds do not manage the trip, but only the signal.
The function is active if the release is energized by an auxiliary power
supply or Ekip Measuring Pro.
Parameters
The following is a description of the parameters:
Parameter Description
Threshold 1
It is possible to do the following:
• Enable the function.
• Set the activation percentage value
Threshold 2
It is possible to do the following:
• Enable the function.
• Set the activation percentage value
Threshold Iw1
It is possible to do the following:
• Enable the function.
• Set the activation value.
• Set the direction.
Threshold Iw2
It is possible to do the following:
• Enable the function.
• Set the activation value.
• Set the direction.
NOTE: the thresholds Iw1 and Iw2 are expressed both as an absolute value (Ampere)
and a relative value (In, nominal value defined by Rating Plug).