Ekip Dip protection release | 8 - Default parameters
8 - Default parameters
Ekip DIP default parameters
The Ekip Dip releases are supplied with the following default parameters, some adjustable with
the front DIPs (protections, Frequency, Neutral), other via front bus (Can, modules).
Protection/Parameter Value
L 1 In; 144 s
S
(1)
Off; 0.1 s
I 4 In
G
(1)
Off; 0.1 s
Frequency 50 Hz
Neutral
Off (for 3P circuit-breaker).
50% (for 4P circuit-breaker)
Hardware trip Disabled
Monitor Time 5 min
Local bus Disabled
Alive LED Disabled (Power LED on fixed)
(1)
Protection S available with LSI and LSIG versions of the release. Protection G available with LSIG version.