HELP
Some led signals indicate connection errors or operational errors that require corrective or
maintenance operations. The following are the suggestions for checking referring to the
preceding LED table:
HELP note Operation
A Contact ABB.
B
Check the connections between release and accessories (rating plug,
trip coil, sensors, etc).
C Normal operation/signalling provided by the release.
D
Error in setting of the dip-switches. Check and correct the following
conditions:
• All the dip-switches of L are in the ON position.
• I1 > I2 or I2 > I3.
• Iu < (2 * In * I1) in the case where InN = 200 %.
E Carry out installation.
F
Connect via Ekip Connect in order to set the local bus or to confirm
maintenance.