171 ADAM-6200 User Manual
Appendix B ADAM-6200 ASCII Commands
#aaDSccnnnn
Name Set AO Startup Value to One Channel
Description Set the startup value to a specified analog output channel in a speci-
fied module.
Syntax $aaDSccnnnn(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal slave
address of the ADAM-6200 module you want to request. (Always 01)
DS represents the analog output channel startup command.
cc (range 00-01) represents the specific channel you want to set the
startup value.
nnnn (range 0000-0FFF) represents the 4-character hexadecimal
startup value of the specific AO channel.
(cr) is the terminating character, carriage return (0Dh).
Response !aa(cr) if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error or communi-
cation error or if the address does not exist.
! delimiter indicating a valid command was received.
? delimiter indicating the command was invalid.
aa (range 00-FF) represents the 2-character hexadecimal slave
address of the ADAM-6200 module you want to request. (Always 01)
(cr) is the terminating character, carriage return (0Dh).
Example Startup value for analog output channel 1 of the ADAM-6224 module
at address 01h is set with a value +10.000. (The AO range of channel
1 is 0~10V)
ASCII Command: $01DS01FFF(cr)
Response: !01(cr)