Rockwell Automation Publication 1766-UM001I-EN-P - June 2015 195
Using ControlFLASH to Upgrade Your Operating System Appendix D
The AB_SNMP.DLL - Enter IP Address dialog box is displayed.
4. Type in the IP address for the processor.
5. Click the Get Info button. If the IP address was previously configured and
the necessary information about the controller is obtained, go to step 9.
6. The AB_SNMP - BOOTP Server dialog box is displayed, indicating that
this IP address has not been configured into the processor.
7. Enter the hardware address of the controller that is being upgraded (as
noted in step 2 of Prepare the Controller for Firmware Upgrade on page
192) and click the OK button.
IMPORTANT
Use the IP address that was configured earlier, or use an available IP
address assigned to by your network administrator.