Publication 1752-UM001A-EN-P - October 2006
50 Configure Local I/O
2. Select the Local Input/Test Output tab.
3. Set the Error Latch Time.
The error latch time applies to all safety inputs and test outputs.
It sets the time to latch the error state when an error occurs in an
input or output. Even if the error is removed, the error state is
always latched for the configured error latch time. The error
latch time is set from 0…65530 ms in 10 ms increments. The
default is 1000 ms.
4. Select a safety input terminal and click Edit.
5. Type an I/O Comment.
The I/O comment typed here is used as an I/O tag name in the
Logic Editor.