EasyManuals Logo

Allen-Bradley SmartGuard 600 User Manual

Allen-Bradley SmartGuard 600
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #53 background imageLoading...
Page #53 background image
Publication 1752-UM001A-EN-P - October 2006
Configure Local I/O 53
Automatic Adjustment of On- and Off-delay Times
If parameters that affect the cycle time are changed after the on- and
off-delays have been set, you may not be able to close the Controller
Properties dialog because of an error in the parameter settings. If this
occurs, you can re-adjust the on-and off-delay times based on the
cycle time using the Adjust valid ON/OFF delays with cycle time value
button on the Local Input/Test Output tab.
Configure Local Test
Outputs
These four independent test outputs can be used in combination with
safety inputs. They can also be set for use as standard output
terminals. The test pulse output features are listed below.
Current monitoring for muting lamp — A wire off or burned out
light bulb can be detected for the T3 terminal only.
Overcurrent detection and protection — To protect the circuit,
an output is blocked when an overcurrent is detected.
ATTENTION
Pulsed outputs must not be used as safety-related outputs (for
example, for the control of safety-related actuators).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley SmartGuard 600 and is the answer not in the manual?

Allen-Bradley SmartGuard 600 Specifications

General IconGeneral
BrandAllen-Bradley
ModelSmartGuard 600
CategoryController
LanguageEnglish

Related product manuals