62    Sequoia Series 
4.8  Power Measurement Subsystem 
This subsystem programs the power measurement capability of the Sequoia Series power source. 
Subsystem Syntax 
MEASure | FETCh 
  [:SCALar] 
    :POWer 
      [:AC]     
        [:REAL]?  Returns real power 
        :APParent?  Returns VA 
        :PFACtor?  Returns power factor 
        :TOTAL?  Returns the total power 
        :REACtive?  Returns the reactive power 
  :DC  Return  the dc component of power measurement 
MEASure:POWer[:AC]?  
FETCh:POWer[:AC]? 
Phase Selectable 
This query returns the in-phase component of power being sourced at the output terminals in kilo watts 
(KW). 
Query Syntax  MEASure[:SCALar]:POWer[:AC][:REAL]? 
Parameters  None 
Examples  MEAS:POW:AC?   
Returned Parameters  <NR2> 
Related Commands  INST:NSEL 
MEASure:POWer:AC:APParent? 
FETCh:POWer[:AC]:APParent? 
Phase Selectable 
This query returns the apparent power being sourced at the output terminals in kilo volt-amperes 
(KVA). 
Query Syntax  MEASure[:SCALar]:POWer[:AC]:APParent? 
Parameters  None 
Examples  MEAS:POW:AC:APP?   
Returned Parameters  <NR2> 
Related Commands  INST:NSEL