SECTION 6 – TESTING AND PLACING IN SERVICE
UL EX3470 ULC EX3470
PAGE 6-4 REV. 11 2014-SEP-01
R-102 Restaurant Fire Suppression Manual
TESTING DETECTION SYSTEM (Continued)
i. Install cover on regulated release assembly and each
regulated actuator assembly and secure with appropriate
fasteners or visual inspection seal. Insert seal (Part No.
197) in each upper and lower cover hole, if applicable. If
system is installed in an OEM enclosure, attach enclosure
cover and secure with appropriate hardware or procedure.
CAUTION
Before installing cover, make certain detection tension
lever is secured in the “DOWN” position to enable
automatic detection and operation of the AUTOMAN
Regulated Release.
j. Record installation date on tag attached to unit and/or in a
permanent file.

Table of Contents

Other manuals for Ansul R-102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ansul R-102 and is the answer not in the manual?

Ansul R-102 Specifications

General IconGeneral
AgentAnsulex Low pH Liquid Fire Suppressant
ActivationAutomatic or manual
Temperature Range32 °F to 120 °F (0 °C to 49 °C)
System TypeWet Chemical
ApplicationCommercial Kitchens
Nozzle CoverageVaries based on hazard and configuration
DetectionThermal or Manual
ApprovalUL 300
Nozzle TypesAppliance specific nozzles
CapacityVaries by cylinder size
MaterialStainless Steel
StandardsNFPA 17A
Cylinder Sizes1.5 to 3 gallons