SECTION 8 – MAINTENANCE EXAMINATION
UL EX3470 ULC EX3470
PAGE 8-6 REV. 11 2014-SEP-01
R-102 Restaurant Fire Suppression Manual
12-YEAR MAINTENANCE EXAMINATION
In addition to performing all of the steps necessary for semi-an-
nual and annual maintenance, the following twelve-year mainte-
nance procedures for single, double, and multiple-tank systems
must be performed.
NOTICE
Under certain circumstances hood and duct
cleaning operations may render your fire
suppression system ineffective due to a
coating of cleaning chemical left on the detec-
tion equipment or mishandling of the system
by cleaning service personnel.
Therefore, it is strongly recommended that
the R-102 system be completely inspected
and serviced by an authorized ANSUL
distributor immediately following any
such cleaning operations.
At twelve-year intervals, the liquid agent
tank(s) must be hydrostatically tested and
refilled with a fresh charge of ANSULEX
Low pH Liquid Fire Suppressant. The date of
manufacture is stamped on the bottom of the
agent tank or on the tank label.
1. Remove the enclosure cover from the AUTOMAN
regulated release assembly and each regulated actuator
assembly.
2. Insert the lock bar (Part No. 14985) or lock pin (Part No.
438031) on the cocked regulated release mechanism. See
Figure 8-9 or Figure 8-10.
LOCK BAR
PROPERLY
INSTALLED
FIGURE 8-9
000321
FIGURE 8-10
009462
3. Remove cartridge from regulated release assembly and
each regulated actuator assembly, install safety shipping
cap, and set aside in a safe location.
CAUTION
Do not reinstall cartridge at this time or system may be
actuated.
4. Remove gasket from cartridge receiver in regulated release
mechanism and each regulated actuator. Check gasket for
elasticity or cuts and replace Gasket (Part No. 181) if neces-
sary. Clean and coat gasket lightly with a good grade of
extreme temperature grease. Reinstall gasket into cartridge
receiver(s).
5. From tank in enclosure: Disconnect the expellant gas piping
or hose from each tank adaptor assembly.
From tank in bracket assembly: Disconnect expellant gas
piping union at each tank adaptor inlet line.
6. Disconnect distribution piping union at each tank adaptor
outlet line.
7. From tank in enclosure: Remove tank.
From tank in bracket assembly: Loosen wingnut, disengage
bracket band, and remove each tank. Keep tank in upright
position to avoid spilling the agent.
8. Loosen tank adaptor/tube assembly and remove.
LOCK PIN
PROPERLY
INSTALLED