EasyManuals Logo

Ansul R-102 Installation And Maintenance Manual

Ansul R-102
188 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #48 background imageLoading...
Page #48 background image
Horizontal Chain Broiler Protection (Continued)
FIGURE 4-54
000247
Overhead Chain Broiler Protection
The R-102 system can use two 1W nozzles for overhead chain
broiler protection. The nozzle is stamped with 1W, indicating
that this is a one-ow nozzle and must be counted as one ow
number.
Overhead protection is only available for chain broilers with
exhaust opening dimensions that are not less than 60% of the
internal broiler length and not less than 60% of the internal
broiler width, to a minimum size of 12 in. x 12 in. (305 mm x
305 mm). Internal broiler size can not be larger than 32 in. x
34 in. (812 mm x 863 mm).
When overhead protection is used, the nozzles must be
centered above the exhaust opening within 4 to 8 in. (101 to 203
mm) of each other and they must be located 10 to 26 in. (254 to
660 mm) above the top of the broiler surface. See Figure 4-55.
FIGURE 4-55
000248
The nozzles may vary in position as long as they are evenly
spaced from the exhaust center and are always 180° opposite
of each other. If the opening is not square, the nozzles must be
positioned along the centerline, parallel to the longest side of the
opening. See Figure 4-56.
FIGURE 4-56
000249
Note: The Metal Blow-off Cap must be used when utilizing
chain broiler protection.
Example No. 1 – Internal broiler size is 24 in. long x 20 in. wide
(609 mm x 508 mm), with an opening of 16 in. x 16 in.
(406 mm x 406 mm).
To determine minimum opening size, multiply the internal
length and the internal width by 0.6:
Length of opening 24 in. x 0.6 = 14.4 in.
(609 mm x 0.6 = 366 mm)
Width of opening 20 in. x 0.6 = 12.0 in.
(508 mm x 0.6 = 304 mm)
The minimum allowable opening for overhead protection
would be 14.4 in. x 12.0 in. (365 mm x 304 mm).
This example would be acceptable for overhead protec-
tion.
Example No. 2 – Internal broiler size is 30 in. long x 24 in.
wide (762 x 609 mm) with an opening of 22 in. x 12 in.
(558 x 304 mm).
To determine minimum opening size, multiply internal
length and internal width by 0.6:
Length of opening 30 in. x 0.6 = 18.0 in.
(762 mm x 0.6 = 457 mm)
Width of opening 24 in. x 0.6 = 14.4 in.
(609 mm x 0.6 = 365 mm)
Minimum allowable opening for overhead protection
would be 18 in. x 14.4 in. (457 mm x 365 mm).
Because this broiler has an opening of 22 in. x 12 in.
(558 mm x 304 mm), the 12 in. (304 mm) width is below
the minimum allowable calculated dimension of 14.4 in.
(365 mm) and therefore would not be acceptable for
overhead protection.
Salamander Broiler Protection
The R-102 system uses three different nozzle locations for
salamander broiler protection. All of the design options require
a one-ow nozzle.
4-8 IN. (101-203 mm)
10-26 IN.
(254-660 mm)
12 IN. (305 mm)
MINIMUM
12 IN. (305 mm)
MINIMUM
MAXIMUM INTERNAL
BROILER SIZE
32 X 34 IN.
(812 x 863 mm)
SECTION 4 – SYSTEM DESIGN
UL EX3470 ULC EX3470
PAGE 4-22 REV. 11 2014-SEP-01
R-102 Restaurant Fire Suppression Manual
MAXIMUM INTERNAL
BROILER SIZE 43 X 31 IN.
(1092 X 787 mm)

Table of Contents

Other manuals for Ansul R-102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ansul R-102 and is the answer not in the manual?

Ansul R-102 Specifications

General IconGeneral
AgentAnsulex Low pH Liquid Fire Suppressant
ActivationAutomatic or manual
Temperature Range32 °F to 120 °F (0 °C to 49 °C)
System TypeWet Chemical
ApplicationCommercial Kitchens
Nozzle CoverageVaries based on hazard and configuration
DetectionThermal or Manual
ApprovalUL 300
Nozzle TypesAppliance specific nozzles
CapacityVaries by cylinder size
MaterialStainless Steel
StandardsNFPA 17A
Cylinder Sizes1.5 to 3 gallons