Anybus Module Objects 103 (258)
Instance Attributes (Instance #12, Domain name)
This instance holds the domain name. Changes are valid after reset.
# Name Access Data Type Description
1 Name Get Array of
CHAR
“Host name”
(Multilingual, see page 106)
2 Data type Get UINT8 07h (= CHAR)
3 Number of elements Get UINT8 30h (48 elements)
4 Descriptor Get UINT8 07h (read/write/shared access)
5 Value Get/Set Array of
CHAR
If read, the actual value will be received. If written, the written
value is reflected in attribute #6 until a reset.
Domain name, 48 characters
6 Configured Value Get Array of
CHAR
Holds the configured value, which will be written to attribute #5
after the module has been reset.
Domain name, 48 characters
Instance Attributes (Instance #13, SMTP Server)
This instance holds the SMTP server address. Changes are valid after reset.
# Name Access Data Type Description
1 Name Get Array of
CHAR
“SMTP server”
(Multilingual, see page 106)
2 Data type Get UINT8 07h (= CHAR)
3 Number of elements Get UINT8 40h (64 elements)
4 Descriptor Get UINT8 07h (read/write/shared access)
5 Value Get/Set Array of
CHAR
If read, the actual value will be received. If written, the written
value is reflected in attribute #6 until a reset.
SMTP server address, 64 characters.
6 Configured Value Get Array of
CHAR
Holds the configured value, which will be written to attribute #5
after the module has been reset.
SMTP server address, 64 characters.
Instance Attributes (Instance #14, SMTP User)
This instance holds the user name for the SMTP account. Changes are valid after reset.
# Name Access Data Type Description
1 Name Get Array of
CHAR
“SMTP user”
(Multilingual, see page 106)
2 Data type Get UINT8 07h (= CHAR)
3 Number of elements Get UINT8 40h (64 elements)
4 Descriptor Get UINT8 07h (read/write/shared access)
5 Value Get/Set Array of
CHAR
If read, the actual value will be received. If written, the written
value is reflected in attribute #6 until a reset.
SMTP account user name, 64 characters
6 Configured Value Get Array of
CHAR
Holds the configured value, which will be written to attribute #5
after the module has been reset.
SMTP account user name, 64 characters
Anybus
®
CompactCom
40 PROFINET IRT Network Guide SCM-1202-023 EN 1.8