USE AND MAINTENANCE MANUAL
ATTILA
57
EN
11.1.2. “TOUCH” VERSION BLAST CHILLER ALARMS
MESSAGE CAUSE EFFECT TYPE OF ERROR SOLUTIONS
E1
Core probe not
properly connected.
If an automatic
programme is running,
switch to manual
programme
Core probe error.
Check the connection
of the core probe to the
EWBC800.
Core probe failure.
Replace the core probe.
E2
Cell probe not properly
connected.
If a manual programme
is running with the
presence of the core
probe (parameter
EP1=1), continue the
manual programme
using the core probe as
cell probe.
If a manual programme
is running with no
core probe (parameter
EP1=0), stop the
manual programme
(stop status).
If an automatic
programme is running,
stop the automatic
programme (stop
status).
Cell probe error.
Check the connection
of the cell probe to the
EWBC800.
Cell probe failure. Replace the cell probe.
E3
Evaporator probe not
properly connected.
If a defrost is in
progress, continuation
of the defrost without
checking the evaporator
probe temperature.
Evaporator probe error.
Check the connection
of the evaporator probe
to the EWBC800.
Evaporator probe
failure.
Replace the evaporator
probe.