USE AND MAINTENANCE MANUAL
ATTILA
67
EN
13.2. PARAMETERS
13.2.1. “DIGITAL VERSION BLAST CHILLER PARAMETERS
PARAMETER DESCRIPTION Min Max Def.4R Def.3R UM
0
When switching to storage The buzzer sounds for indicated
sec.
0 1 10 10 no.
1
Door Presence
0=Door absent
1=Door present.
0 1 1 1 no.
2
Fan in blasting
0= in parallel with the compressor
1=always on.
0 1 1 1 no.
3 Enabling core probe. 0 1 1 1 no.
4 Enabling negative blasting. 0 1 1 1 no.
5 Enable Defrosting. 0 1 1 1 no.
6
Stops utilities with open door
0=Compressor+Fans
1=Fans.
0 1 1 1 no.
7
RL2 configuration
0= Defrosting
1=Fans+Defrosting.
0 1 1 1 no.
8 Adjustment hysteresis. 1 20 3 3 °C
9 Compressor Protection Off/On (also valid at reset). 0 99 2 2 min
10 Compressor Protection On/On. 0 99 3 3 min
11 Defrosting Duration. 0 99 10 10 min
12 Dripping Duration. 0 99 3 3 min
13 Core Set for positive blasting. -50 99 3 3 °C
14 Core Set for negative blasting. -50 99 -18 -18 °C
15 Chamber Set for positive blasting. -50 99 -2 -2 °C
16 Chamber Set for negative blasting. -50 99 -35 -35 °C