Configuration for Autroprime
AutroGuard Multicriteria Protector Series V-430, V-530, V-100, V110 and V-120,
AutroGuard-Technical-Handbook, Doc-1004339-4, 2022-12-09,
Autronica Fire and Security AS
Page 100
13.4.2 Heat Response Category Day Mode
• From the Service menu, select Unit Configuration, then scroll
down until you find Points.
For heat detection, the following Heat Response Categories are
available:
• A1
• A1S
• A1R
• A2S
• B
• C (applies to heat only)
• Heat alarm disabled (applies to Multi only)
• For the chosen Protector, select the Heat Reponse Category for
Day Mode.
13.4.3 Sensitivity Class Day Mode
• From the Service menu, select Unit Configuration, then scroll
down until you find Points.
AutroGuard® protectors provide the following Sensitivity settings:
• High
• Medium
• Low
• For the chosen Protector, select the Sensitivity Class for Day
Mode.
13.4.4 Operation Class Night Mode
• From the Service menu, select Unit Configuration, then scroll
down until you find Points.
AutroGuard® protector’s provide the following Operation Classes:
• Smoke only
• Heat only
• Multi
• For the chosen Protector, select the Operation Class for Night
Mode.
The Operation Classes that can be chosen depends on the type of
point, i.e. MultiSensor with heat, MultiSensor only, Heat only.