Technical Specifications
AutroGuard Multicriteria Protector Series V-430, V-530, V-100, V110 and V-120,
AutroGuard-Technical-Handbook, Doc-1004339-4, 2022-12-09,
Autronica Fire and Security AS
Page 22
Operating temperature for UL variants
10% - 95% RH (non-condensing)
Maximum 2,5mm
2
/AWG14
Short circuit Isolator (Base)
Maritime approval (M variants)
UL certification/ETL listing
(/UL variants are not EN54 approved)
Smoke and Multi: UL 268, ULCS529
Heat (only Heat Response Category A1 is certified):
UL 521, ULC S530
For details on certifications, see Autronica’s product web.
4.2 Integrated Sounder
Technical specifications INTEGRATED SOUNDER
HIGH VOLUME : Maximum 93 dBA at 1m range
HIGH VOLUME: 6,25mA (incl. 120µA for protector and base)
LOW VOLUME: 2,63mA (incl. 120µA for protector and base)
160µA (+ 120µA for protector and base)
16 standard tone types/ 16 standard tone types/frequencies and
corresponding ringing patterns are available (see next chapters). In
addition, ringing patterns for the standard tone types/frequencies
can be configured to meet other user requirements.