Configuration for Autroprime
AutroGuard Multicriteria Protector Series V-430, V-530, V-100, V110 and V-120,
AutroGuard-Technical-Handbook, Doc-1004339-4, 2022-12-09,
Autronica Fire and Security AS
Page 99
13.4 Individual Settings
• From the Service menu, select Unit Configuration, then scroll
down until you find Points.
A point representing a Protector (series V-430 or V-530) is indicated,
as for example, V-430-S-VADW, V-530-S etc. in the display.
For a selected Protector, you can configure the following:
• (Override Delay and Dependency: Yes/No)*
• Operation Class Day Mode
• Heat Response Category Day Mode
• Sensitivity Class Day Mode
• Operation Class Night Mode
• Heat Response Category Night Mode
• Sensitiviy Class Night Mode
• Enable Autromatic Test Mode
• Use LED Alive Blink
• Use LED Blink on Alam
• External Output Follow Alarm
• Cover Detection Sensitivity
NOTE: Requires license for Cover Detection Sensitivity.
* Applies to legacy detectors and AutroGuard protectors – not
specific for AutroGuard protectors, ref. to AutroPrime Configuration
Handbook)
13.4.1 Operation Class Day Mode
• From the Service menu, select Unit Configuration, then scroll
down until you find Points.
AutroGuard® protector’s provide the following Operation Classes:
• Smoke only
• Heat only
• Multi
• For the chosen Protector, select the Operation Class for Day
Mode
The Operation Classes that can be chosen depends on the type of
point, i.e. MultiSensor with heat, MultiSensor only, Heat only.