Configuration for Autroprime
AutroGuard Multicriteria Protector Series V-430, V-530, V-100, V110 and V-120,
AutroGuard-Technical-Handbook, Doc-1004339-4, 2022-12-09,
Autronica Fire and Security AS
Page 102
13.4.8 Use LED Alive Blink
From the Service menu, select Unit Configuration, then scroll
down until you find Points.
For the chosen Protector, select Yes or No
13.4.9 Use Blink On Alarm
From the Service menu, select Unit Configuration, then scroll
down until you find Points.
For the chosen Protector, select Yes or No
13.4.10 External Output Follow Alarm
From the Service menu, select Unit Configuration, then scroll
down until you find Points.
For the chosen Protector, select Yes or No.
Note that by means of the AutroClient, these functions can be
configured globally for all protectors.
13.4.11 Cover Detection Sensitivity
NOTE: Requires license for Cover Detection Sensitivity. If the
hardware of the Protector does not have this license, the menu
choice “Cover Detection Sensitivity” will not appear in the display.
AutroGuard® protectors with Cover Detection provide the following
sensitivity classes:
Off
Normal
High
Select the relevant Cover Detection Sensitivity for each protector.