Configuration for AutroSafe
AutroGuard Multicriteria Protector Series V-430, V-530, V-100, V110 and V-120,
AutroGuard-Technical-Handbook, Doc-1004339-4, 2022-12-09,
Autronica Fire and Security AS
Page 90
12.7 AutroGuard Individual Settings
12.7.1 Fire Alarm Devices
AutroGuard® protectors with visual and/or audible alarm devices
(FADs), may include the following:
• Sounder
• Sounder and visual alarm device
• Voice alarm (not yet available)
• Voice alarm (not yet available) and visual alarm device
• Visual alarm device
• From the system view, select the AutroGuard® Protector
• Click the dropdown button and select the relevant Alarm Device
12.7.2 Automatic Test Mode
The Automatic Test Mode is used during manual testing with a test
kit (see chapter 14.3.3).
Automatic Test Mode can be enabled (ON) or disabled (OFF) per
protector by means of the Configuration Tool.
• From the system view, select the AutroGuard® Protector
• To enable automatic test mode for a protector, check the
checkbox Automatic Test Mode
Refer to chapter 14.3.3 Automatic Test Mode.