Configuration for Autroprime
AutroGuard Multicriteria Protector Series V-430, V-530, V-100, V110 and V-120,
AutroGuard-Technical-Handbook, Doc-1004339-4, 2022-12-09,
Autronica Fire and Security AS
Page 101
13.4.5 Heat Response Category Night Mode
From the Service menu, select Unit Configuration, then scroll
down until you find Points.
For heat detection, the following Heat Response Categories are
available:
A1
A1S
A1R
A2S
B
C (applies to heat only)
Heat alarm disabled (applies to Multi only)
For the chosen Protector, select the Heat Reponse Category for
Night Mode.
13.4.6 Sensitivity Class Night Mode
From the Service menu, select Unit Configuration, then scroll
down until you find Points.
AutroGuard® protectors provide the following Sensitivity settings:
High
Medium
Low
For the chosen Protector, select the Sensitivity Class for Night
Mode
13.4.7 Enable Automatic Test Mode
From the Service menu, select Unit Configuration, then scroll
down until you find Points.
The Automatic Test Mode is used during manual testing with a test
kit (see chapter 14.3.2).
Automatic Test Mode can be enabled (ON) or disabled (OFF) per
protector. The default setting is OFF.