Configuration for Autroprime
AutroGuard Multicriteria Protector Series V-430, V-530, V-100, V110 and V-120,
AutroGuard-Technical-Handbook, Doc-1004339-4, 2022-12-09,
Autronica Fire and Security AS
Page 101
13.4.5 Heat Response Category Night Mode
• From the Service menu, select Unit Configuration, then scroll
down until you find Points.
For heat detection, the following Heat Response Categories are
available:
• A1
• A1S
• A1R
• A2S
• B
• C (applies to heat only)
• Heat alarm disabled (applies to Multi only)
• For the chosen Protector, select the Heat Reponse Category for
Night Mode.
13.4.6 Sensitivity Class Night Mode
• From the Service menu, select Unit Configuration, then scroll
down until you find Points.
AutroGuard® protectors provide the following Sensitivity settings:
• High
• Medium
• Low
• For the chosen Protector, select the Sensitivity Class for Night
Mode
13.4.7 Enable Automatic Test Mode
• From the Service menu, select Unit Configuration, then scroll
down until you find Points.
The Automatic Test Mode is used during manual testing with a test
kit (see chapter 14.3.2).
• Automatic Test Mode can be enabled (ON) or disabled (OFF) per
protector. The default setting is OFF.