Functional Description
AutroGuard Multicriteria Protector Series V-430, V-530, V-100, V110 and V-120,
AutroGuard-Technical-Handbook, Doc-1004339-4, 2022-12-09,
Autronica Fire and Security AS
Page 34
5.4 Sensitivity Classes for Environmental Adaptivity
The AutroGuard® Multicriteria
Protector can be programmed to
different Sensitivity Classes, with
sensitivity settings covering
different environments.
Clean environments, for example laboratories,
data rooms etc.
Normal environments, for example offices and
hospitals etc.
Industrial environments, for example,
factories and warehouses etc.
By choosing a sensitivity class that suits the environment, it is
possible to achieve an accurate and reliable system, providing the
optimal detection, whilst virtually eliminating false alarms.
High, medium and low sensitivity classes comply with the
EN54-7/29.
For information on the configuration of Sensitivity Settings, refer to
chapter 12.7.6.
5.5 Operation Classes
The AutroGuard® Multicriteria Protector can be set to three different
Operation Classes, allowing you to choose the protector’s detection
method and calculation. The Operation Classes are as follows;
Optical and heat detection
For information on the configuration of Operation Classes, refer to
chapter 12.7.5.