Configuration Recommendations
AutroGuard Multicriteria Protector Series V-430, V-530, V-100, V110 and V-120,
AutroGuard-Technical-Handbook, Doc-1004339-4, 2022-12-09,
Autronica Fire and Security AS
Page 76
11.4 Freezers and Cold Stores
In general, smoke detection is not recommended in cold store areas
due to risk of condensation.
Configuration of AutroGuard in Freezers and cold stores without
temperature fluctuations:
Operation Class
HEAT
Sensitivity Class
Heat response Category
A1R
Configuration of AutroGuard in Freezers and cold stores with
temperature fluctuations:
Operation Class
HEAT
Sensitivity Class
Heat response Category
A2S
11.5 Clean Rooms and Computer Rooms
In general, early detection is required in Clean/Computer/Server
Rooms.
Configuration of AutroGuard in Cleam Rooms and Computer
Rooms with early detection of small amounts of smoke:
Operation Class
MULTI
Sensitivity Class
HIGH
Heat response Category
A1
11.6 Table Overview Applications/Settings
See next pages.