Preparing for Configuration
AutroGuard Multicriteria Protector Series V-430, V-530, V-100, V110 and V-120,
AutroGuard-Technical-Handbook, Doc-1004339-4, 2022-12-09,
Autronica Fire and Security AS
Page 71
10.4.1 Alternative A - Using a QR code reader
• Prepare a list with all tag names and DZ text on an Excel sheet
• Scan the QR code for each base
• Ensure that the serial number is linked to the correct tag name
• Place the tag name label onto the base’s tagholder
• Install all AutroGuard bases
10.4.2 Alternative B - Using the rip off label
• Prepare a list with all tag names and DZ text on an Excel sheet
• Print the list
• Rip off the label from the base (see 10.3.2)
• Insert the rip off label beside the correct tag name (a unique
description assigned to the protector’s location) on the printout
• Place the correct tag name label onto the base’s tagholder
• Install all AutroGuard bases
10.5 Scanning each loop with AS2000
AS-2000 is connected to the detection loop via the BSL-310 module in
an AutroSafe panel, or by means of an external interface unit, WAS-
2000.
• When connected, press the START button in the Topology
window (AS-2000).
AS-2000 will detect all bases connected to the selected loop driver
and present them graphically in a correct electrical sequence. If any
breaks on the loop’s minus wire or short-circuits are detected, see
Troubleshooting, chapter 10.9