EasyManua.ls Logo

Autronica AutroGuard Multicriteria Protector V-430 Series - Connecting Loop Cables

Autronica AutroGuard Multicriteria Protector V-430 Series
126 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mounting Instructions
AutroGuard Multicriteria Protector Series V-430, V-530, V-100, V110 and V-120,
AutroGuard-Technical-Handbook, Doc-1004339-4, 2022-12-09,
Autronica Fire and Security AS
Page 56
9.3 Connecting Loop Cables
9.3.1 Cable Requirements
The following cable requirements apply:
Minimum 0,14mm
2
/AWG26
Maximum 2,5mm
2
/AWG14
Connection Capacity
Conductor cross section, solid
0,14 mm
2
to 2,5 mm
2
Conductor cross section, flexible
0,14 mm
2
to 2,5 mm
2
Conductor cross section, flexible, with ferrule without plastic
sleeve
0,25 mm
2
to 1,5 mm
2
Conductor cross section, flexible, with ferrule with plastic
sleeve
0,25 mm
2
to 1,5 mm
2
Conductor cross section AWG/kcmill
26 to 14
Be aware that the use of ferrules changes the minimum and
maximum cable dimensions 0,25 mm
2
to 1,5 mm
2
.
When connecting and possibly adjusting a solid conductor of 2,5
mm
2
, the mechanical lateral forces, which can affect the terminal
block, have to be absorbed by lateral support. Therefore, the wires
must be supported by the cable holders as shown in next chapter.
Note that the colors of the cables/wires shown in this handbook
(red/black) is used as a reference only. The colors may be different
and will vary depending on the installation, applicable standards or
local regulations.

Table of Contents

Related product manuals