Configuration Recommendations
AutroGuard Multicriteria Protector Series V-430, V-530, V-100, V110 and V-120,
AutroGuard-Technical-Handbook, Doc-1004339-4, 2022-12-09,
Autronica Fire and Security AS
Page 74
11. Configuration Recommendations
11.1 Introduction
The configuration of Sensitivity, Operation Classes and Heat
Response Categories is described in chapter 5.4, 5.5 and 5.6,
respectively. These settings allow you to fine tune the AutroGuard®
protectors to avoid unwanted alarms, and at the same time give the
earliest possible detection.
Below you will find the recommended settings suitable for different
applications and rooms with the presence of various nuisance
sources. Note that the environment in rooms and applications may
vary. The below tables describe Autronica’s recommendations based
on general information only. Local considerations need to be made.
Nuisance source
Operation
class
Sensitivity
class
Heat
response
STEAM from showering,
ironing, cleaning etc.
MULTI
LOW
DISABLED
COOKING FUMES without
risk of steam
SMOKE
LOW
DISABLED
AIRBORN DUST
SMOKE
LOW
DISABLED
ARTIFICIAL SMOKE /
THEATER SMOKE
SMOKE
LOW
DISABLED
CONDENSATION in
freezers, tunnels, and in
general where hot and
cold air meets
HEAT
A2S
Short bursts of nuisance
like opening dishwasher,
opening bathroom door,
opening oven etc.
MULTI
LOW
TBD by
application