Configuration for Autroprime
AutroGuard Multicriteria Protector Series V-430, V-530, V-100, V110 and V-120,
AutroGuard-Technical-Handbook, Doc-1004339-4, 2022-12-09,
Autronica Fire and Security AS
Page 98
13.3 Global Settings
13.3.1 Sound Patterns
The configuration of sound patterns is a global setting for the entire
system. The tones that are available are listed in chapter 0 (Technical
Specifications).
From the Service menu, select System Settings, then scroll down
until you find Sound Patterns.
Note that if at least one legacy loop sounder exists on the Autroprime
detection loop, it will not be possible to select any of the tones that
are otherwise available for the AutroGuard Protector.
The parameters “Delay” and “Sound Pattern” (named “Pulse Pattern”
in AutroSafe) are set to predefined default values according to the
selected Sound Tone.
The Sound Tones “Dutch Slow Whoop” and “Swedish All Clear” have
a predefined “Delay” and “Sound Pattern”, thus the user cannot
change these parameters.
13.3.2 Visual Alarm Device (VAD)
The configuration of VAD is a global setting for the entire system.
From the Service menu, select System Settings, then scroll down
until you find VAD Settings.
The settings are:
VAD Intensity: Low (default) and High
VAD Flash Rate: Every two seconds (0,5Hz, default) or Every
second
Note that the different settings have different current consumptions.
Always take into consideration that a high intensity will draw more
current than a low intensity, and high intensity will lead to fewer
units per detection loop.