Configuration Recommendations
AutroGuard Multicriteria Protector Series V-430, V-530, V-100, V110 and V-120,
AutroGuard-Technical-Handbook, Doc-1004339-4, 2022-12-09,
Autronica Fire and Security AS
Page 77
Application
Class
tivity
Category
challenges, low
pollution and stable
temperature
areas. If the office area
has some air pollution,
medium sensitivity may
be selected. Where
there is risk for higher
temperature than 56'C
(e.g atriums where sun
can heat up), Heat
response category B
Room/Computer
Room/Server
Room
there is a need for
early detection.
Clean air and stable
Highest sensitivity within
EN54
Temperature
increase, Cooking
fumes
ovens releasing very
warm air, often with
steam, smoke or cooking
fumes. With smoke
sensitivity set to LOW,
the AutroGuard will have
a good but a bit reduced
sensitivity while the
DYFI3D will discriminate
unwanted alarms from
steam and cooking
fumes. If heat detection
is required A2S is the
preferred heat response
category. This requires
that ambient
temperature is below
reduced
sensitivity
steam, heat ramps
apartment buildings
where the protector is
installed near e.g. the
stove. The sensitivity is
reduced, and heat
increase will not trigger
normal sensitivity
steam, heat ramps
apartment buildings
where the protector is
installed out of the
immediate kitchen area.
The sensitivity is normal,
but heat increase will