Configuration Recommendations
AutroGuard Multicriteria Protector Series V-430, V-530, V-100, V110 and V-120,
AutroGuard-Technical-Handbook, Doc-1004339-4, 2022-12-09,
Autronica Fire and Security AS
Page 78
Typical
Application
Typical Challenges
Description
Operation
Class
Sensi-
tivity
Class
Heat Resp.
Category
Apartment
Building,
bedroom
Need fast response
in clean
environment
Early detection, no
special issues with
nuisance alarm sources
Multi
High
A1
Hotel Room with
good ventilation,
no smoking
Steam from
bathroom comes
out in the hotel
room.
For modern hotels with
good ventilation and
minimal risk of steam
and cigarette smoke.
Increased sensitivity and
response to fire.
Multi
High
A1S
Hotel Room
where shower
steam may be
present
Steam from
bathroom comes
out in the hotel
room
Reduced sensitivity
when there is a risk of
steam
Multi
Low
A2S
Hotel Room,
smoking allowed
Cigarette smoke
Standard sensitivity
when there is no risk of
steam.
Multi
Medium
A1S
Freezer and Cold
Store without
temperature
fluctuations
In general, smoke
detection is not
recommended in cold
store areas due to
condensation. Mounting
the detector far into the
cold store makes sure
that the detector will not
see a temperature
increase while opening
doors or gates. In this
case its recommended to
use HEAT response
category A1R, giving
quick alarm response to
a heat increase (rate of
rise).
Heat
Disabled
A1R
Freezer and Cold
Store with
temperature
fluctuations
Warm air coming in
through a door or
gate that is opened.
Condensation
In general, smoke
detection is not
recommended in cold
store areas due to
condensation. Heat
detection in class A2S
makes sure the detector
is unaffected by opening
doors or gates letting
warm air into the cold
store. A2S gives slower
response time since the
heat needs to reach
approximately 58
degrees for alarm.
Heat
Disabled
A2S
Parking Garage
Exhaust,
condensation, dust
Point smoke detectors
might not always be the
best option for parking
garage, due to the
Multi
Low
A2S

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autronica AutroGuard Multicriteria Protector V-430 Series and is the answer not in the manual?

Autronica AutroGuard Multicriteria Protector V-430 Series Specifications

General IconGeneral
BrandAutronica
ModelAutroGuard Multicriteria Protector V-430 Series
CategoryFire Alarms
LanguageEnglish

Related product manuals