Instruction Manual w VERTICUS 5 Compressor Units
A-60
11.4.12. Setup
The Setup page (Fig. 67) enabless the setting of various
parameters:
Language: German, English, Russian, etc.
Pressure unit: bar, Mpa, psi, psig
If you still use psi or psig please note that
Mpa is the only pressure unit having
international validity.
Temperature unit: °Celsius, °Farenheit, Kelvin
If you still use
o
C or
o
F, please note that
K is the only temperature unit having
international validity.
Sensors
SECURUS
SECCANT CAN
Valves
Display setting
Backup setting
Bus-Com.
Logger
B-Messenger
Setup system
Sensors
By scrolling in the sensors pages, the settings of the
sensors will be displayed. Sensor settings can only be
modified in the configuration password level resp. by
customer service.
The number of its analogue channel (Ch 0, Fig. 68) is dis
played on the right side, next to the designation of the sen
sor.
MBU is the minimum settable value, MBO is the maximum
settable value, < the lower alarm value, > the upper alarm
value, << the lower switch-off value >> the upper switch-off
value. The current value is shown under the = symbol.
Lower and/or upper switch-off values assume the function
of safety switch-off.