03/12 EM-ABS-01 for ACU 91
8.1.7 Adjustment
Due to component tolerance, it can be necessary to ad
j
ust the analo
g
input. This is
done via parameter
Adjustment 568.
Adjustment 568
Function
0 - No adjustment Standard operation
1 - Adjustment 0 V
Adjustment of the measurement with an analog signal
of 0 V.
2 - Adjustment 10 V
Adjustment of the measurement with an analog signal
of 10 V.
Example of the adjustment of an analog input with a voltage signal:
Note: The measurements for the ad
j
ustment are to be done with a suitable
measuring instrument and the correct polarity.
If not, faulty measurements can result.
Apply 0 V to the analog input; e.g. with a bridge from the terminal of the ana-
log input X410A.6 to terminal X210B.7 (earth/GND) of the frequency inverter.
Select operation mode “1 - Adjustment 0 V”.
Apply 10 V to the analo
g
input, e.
g
. with a brid
g
e from the terminal of the
analog input to terminal X210B.5 (reference output 10 V) of the frequency in-
verter.
Select operation mode “2 - Ad
j
ustment 10 V”. This completes the ad
j
ustment
of the analog input.
8.1.8 Filter time constant
The time constant of the filter for the reference analog value can be set via the para-
meter
Filter time constant 561.
T
he time constant indicates the time durin
g
which the input si
g
nal is avera
g
ed by
means of a low pass filter, e.g. in order to eliminate fault effects.
The setting range is between 0 ms and 5000 ms in 15 steps.
Filter time constant 561
Function
0 - Time constant 0 ms
Filter deactivated – analog reference value is for-
warded unfiltered
2 - Time constant 2 ms Filter activated – avera
g
in
g
of the input si
g
nal via
the set value of the filter time constants Factory
setting: 8 ms.
4 - Time constant 4 ms
8 - Time constant 8 ms
16 - Time constant 16 ms
32 - Time constant 32 ms
64 - Time constant 64 ms
128 - Time constant 128 ms
256 - Time constant 256 ms
512 - Time constant 512 ms
1000 - Time constant 1000 ms
2000 - Time constant 2000 ms
3000 - Time constant 3000 ms
4000 - Time constant 4000 ms
5000 - Time constant 5000 ms

Table of Contents

Other manuals for BONFIGLIOLI Active Cube

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the BONFIGLIOLI Active Cube and is the answer not in the manual?

BONFIGLIOLI Active Cube Specifications

General IconGeneral
BrandBONFIGLIOLI
ModelActive Cube
CategoryInverter
LanguageEnglish

Related product manuals