DS7200V2-EXP | Installation Guide | 3. Control Panel
Programming
EN | 103
Remote Programming Callback Number Alternate Communication Options
Address: 3538
Default: 0
Selections:
- 0 = No Alternate Communication
- 1 = Enable Alternate Communication
If an IP address is entered into the Remote Programming Callback Number addresses (Addresses
0181-0212), RPS can be used to program the control panel over an Ethernet network.
Select “1” if an IP address is entered into the Remote Programming Callback Number addresses.
Alternate Communication Wait Time
Address:
- IP Address 1, Destination 1: 3507 to 3509
- IP Address 2, Destination 1: 3515 to 3517
- IP Address 1, Destination 2: 3523 to 3525
- IP Address 2, Destination 2: 3531 to 3533
Default: 0, 1, 3
Selections: 0 to 1665 sec
Use this parameter to define how long the DX4020 waits before attempting to send additional reports
to the ARC.
This parameter uses three addresses for each routing destination. In the first address, enter the 100’s
value (this value is multiplied by 100). In the second address, enter the 10’s value (this value is
multiplied by 10). In the third address, enter the 1’s value (the 100’s and 10’s values are added to the
1’s value).
The following example shows how to get an alternate communication wait time of 555 sec for IP
Address 1, Destination 1:
[5 x 100] + [5 x 10] + 5 = 555 sec
If the “Use ARC Acks” option is enabled and the alternate communication wait time is less than 5 sec,
a minimum of 5 sec is automatically used.
You can enter a value between 0 and 15 for each alternate communication wait time address.
Address 3507
Entry
Address 3508
Entry
Address 3509
Entry