3.2.4 Global Reporting Options
These parameters configure the reporting for all areas, all zones, and all users.
Global Reporting Options
• Address: 0221
• Default: 1
• Selections: 0, 1, 3, 5, 7, 9, 11, 13, 15
Enter This Data Digit to Select Options
Burg Alarm after Two Failed Attempts
• Local Only: The control panel sends no reports.
• Enable Reporting: If this option is enabled, the control panel sends reports as programmed
provided that at least one phone number (or IP address) has been programmed for at least one
Routing Destination (see Phone Number 1 (2) for Destination 1 (2) on page 50). Reporting options
can be enabled and disabled in other parameters. See Open/Close Reporting Options on page 64,
and Area # Opening {89-96}/Closing {42-67} Reporting Options on page 66 for more information.
• Extend Handshake: If this option is enabled, the control panel finishes dialing the ARC receiver
and waits for a ‘handshake’ tone from the receiver. The handshake is the first thing the receiver
sends after answering the phone. Typically each reporting format the receiver supports has its
own handshake tone. If a receiver supports several formats, it sounds the handshake tones one at
time. Choosing this option extends the time the control panel waits for a handshake from the ARC
receiver from 45 to 60 sec.
Do not change the Extend Handshake option unless advised by Bosch Technical Service.
• Delay Alarm Output: If this option is enabled, the control panel delays burglary alarm output until
communication to the ARC receiver is complete or there are two failed dialing attempts. The
delayed alarm output functions are 1|8, 1|9, and 1|10 (see Table 34 for descriptions of output
function types). Bell Time is not delayed, and begins at the alarm event. If Bell Time is set at 3 min
or less, alarm output delayed by this option may be very short (less than 1 min), or the alarm
output may not activate at all. See Output Parameters on page 86 for a complete description of
output functions. The keypad sounder is not delayed by this option.
In order to use the Delay Alarm Output option, the Alarm Event Abort option must be
disabled. See “Options 1, Zone Function ##” in the DS7200V2 Expert Programming Guide
(P/N: 4998153891).