• Burg Alarm After Two Failed Attempts: If this option is enabled, a steady alarm output sounds
after two failed attempts to transmit a burglary alarm report from any zone when its area is armed.
Alarm output is provided even if the zone is not programmed for alarm output. Bell Time must be
programmed with at least 3 min to use this option. Disable this option to prevent an alarm output
from silent zones even when the system fails to communicate with the receiver. This option only
applies to output types 1|8 (Alarm – All On, Perimeter Only & Partial On; non-fire 24-hr alarms);
1|9 (Alarm – Perimeter Only and Partial On Modes; non-fire 24-hr alarms) and 1|10 (Alarm –
controlled and 24-hr zones-fire and non-fire). See Output Parameters on page 86 for alarm
configuration.
The burg alarm output activates after two failed communication attempts even if the zone
is set for silent operation.
Call for Service Text
• Address: 1266 to 1297
• Default: Blank
• Selections: See Table 21
This parameter provides 16 characters of programmable text to be displayed in the second line of the
display whenever the first line shows “Call for Service.” It is also displayed when the keypad is
extinguished and the “Extinguish Mode Displays Date” option is enabled. See Keypad Response
Options on page 75 for information on the Extinguish Mode options.
All control panel text is programmed from the text keypad in a special text-programming mode. See
Text Entry Addresses on page 47 for text programming instructions.
The following are possible entries for the second line of text:
• ARC phone number.
• Preferred phone number called for service.
• “Press 0 to view.” This tells users which key to press to see system trouble details. See Call for
Service Details on page 125 for more information.