DS7200V2-EXP | Installation Guide | 3. Control Panel
Programming
EN | 61
Automatic Test {137} Report Interval
Address: 0254
Default: 3 (7 Days)
Selections:
- 0 = No Automatic Test
- 1 = 1 Hour
- 2 = 1 Day
- 3 = 7 Days
- 4 = 28 Days
Enter zero (0) to disable the Automatic Test {137} report function.
The one-hour interval increments on the minute. For example, if you set the Automatic Test Time
parameter to 1020 (10:20 AM), the Automatic Test Interval is one hour, and left programming mode at
11:10 AM, then the control panel sends a test report at 11:20 AM (less than one hour after leaving
programming mode). The next test report would come at 12:20 PM.
The one-day, seven-day, and 28 day intervals are incremented at midnight (2400). For example, if you
set the Automatic Test Time parameter to 1020 (10:20 AM), the Automatic Test Interval is one day,
and left programming mode at 10:10 AM, then the control panel does not send a test report until
10:20 AM the next day (after the one-day interval increment at midnight).