Alarm Output Option for ABC Keys
• Address: 0700
• Default: 0
• Selections: 0 to 7
Enter This Data Digit to Select Options
Alarm Output Options for ABC Keys
No Alarm Output for ABC Keys
This parameter assigns an alarm output option to the ABC keys. The alarm output activates for the
response type assigned to each key. This is a global parameter that affects all areas.
ABC Key Reports/Ack Beep Options
• Address: 0701
• Default: 0
• Selections: 0 to 15
Enter This Data Digit to Select Options
ABC Keys Report & Ack Beep Options
No Alarm Report for ABC Keys
Enable ABC Keys Reporting
Acknowledgement Beep for [A] Key
Acknowledgement Beep for [B] Key
Acknowledgement Beep for [C] Key
This is a global parameter that affects all areas.
• Enable ABC Keys Reporting: If this option is enabled, the keys report as follows:
- [A] Key reports as Zone 100
- [B] Key reports as Zone 101
- [C] Key reports as Zone 102
• Acknowledgement Beep for ABC Keys: If this option is enabled, the keypad beeps when the ARC
receiver acknowledges a report. If the key is not programmed for reports, the beep occurs on