102 en | Installation Modular Fire Panel
09.2017 | 11.3 | F.01U.028.089 System Information Bosch Sicherheitssysteme GmbH
24 V
1
Figure4.55: BCM‑0000‑B Battery Controller Module
Top connections, from left to right
24V + | - Switch output +24V max. 2.8A (battery buffered, optional)
24V + | - Switch output +24V max. 2.8A (battery buffered, optional)
Lower connections, from left to right
MAIN + | - Power supply unit connection
MAIN FAULT Signal input for power supply unit fault
BAT1 + | - Battery pair 1 connection
BAT2 + | - Battery pair 2 connection
FAULT AC - Switch output for mains fault
FAULT BAT - Switch output for battery fault
FAULTΣ - Switch output for collective fault
FAULT +24V Switch output +
Notes
The module can only be used with the MPC Panel Controller from software version 2.1
onwards.
If the FPA-5000 Fire Panel is not supplied with mains power, it can only be started
if a battery pair is connected to BAT1 and
no second battery pair is connected to BAT2.