Modular Fire Panel Installation | en 103
Bosch Sicherheitssysteme GmbH System Information 09.2017 | 11.3 | F.01U.028.089
If batteries are connected to the BAT2 connection on the module, the system will
report a battery fault and will not start. This battery fault can only be reset if the
FPA-5000 Fire Panel is supplied with mains power and the BAT 2 connection is
configured.
If the FPA-5000 Fire Panel is not supplied with mains power for an extended period,
ensure that the batteries are disconnected.
When using the module in the FPP‑5000 External Power Supply, only one battery pair can
be charged (see FPP‑5000 External Power Supply Unit Kit 24V/6A, page 121).
Refer to the configuration information in Configuration of BCM Battery Controller Module,
page 36.
The technical data can be found in BCM‑0000‑B Battery Controller Module, page 150.