Programming Item Item
Number
Selections Manuf.
Default
Test Report Minute 144 0 to 59 0
Test Report Day of Week 145 0 to 6, where 0 = Sunday and 6 = Saturday 0
Test Report Day of Month 146 1 to 28 1
Clear Confirmed Alarm Memory 147 0 = User can clear a confirmed alarm
1 = Only the installer can clear a confirmed alarm
0
Arming Beeps/Graduated
Annunciation
148 0 = No arming beeps or outputs during Entry Delay
1 = Outputs activate during Entry Delay, but no
arming beeps occur.
2 = Sound arming beeps, but outputs do not
activate during Entry Delay
3 = Sound arming beeps, and outputs activate
during Entry Delay
0
Wireless Jam Detect Level 150 0 to 15 12
Wireless Device Supervision Interval 151 1= 1 Hour
2= 2 Hours
3= 4 Hours
4= 12 Hours
5= 24Hours
6= 2.5 Hours
Key Fob Arming 153 0 = Do not turn system on if there are faulted
points
1 = Force arm faulted points if the number of
faulted points is within the range set in Expert
Programming Item Number 125
2 = Force arm faulted points even if the number of
faulted points exceeds the range set in Expert
Programming Item Number 125
0
Two-Way Voice Session
Configuration
158 0 = Allow at any time
1 = Allow only during alarm conditions
0
Start Arming with Faulted Points 159 0 = Force arm all faulted points
1 = Exit Delay starts with faulted points
1
Speak Active Faults 160 0 = "Call for Service" announced
1 = Fault condition announced
0
Wireless Transmission Attenuation 161 Temporary attenuation for installation and
maintenance only. Not intended for normal
operation.
0 = None (normal operation)
1 = 3 dB
2 = 6 dB
3 = 9 dB
4 = 12 dB
0
50 en | Programming Easy Series Control Panel