Appendix E.  Log Files 
TABLE E-2.  Communication Status Log Messages 
Message Text  Message Meaning  User Response to Message 
PakBus framing error  LoggerNet received data 
from the link that cannot 
be verified to be part of a 
PakBus packet. 
Some possible causes:  the 
datalogger program or its settings 
are configured to write data on the 
port on which you are attempting to 
connect, there is a mismatch in baud 
rates between your computer serial 
port and the datalogger, the link is 
dropping sequences of characters 
from transmission because the CPU 
on the computer is heavily loaded or 
because of faulty USB drivers.  
Possible solutions: change the port 
you are using to communicate, try 
using a slower baud rate to 
communicate with the datalogger, 
use Windows Task Manager to 
determine whether there are 
processes that are loading down 
your CPU, check to see if there is an 
updated driver for your USB/RS232 
adapter. 
Invalid low level signature  The packet received 
from the device got 
corrupted and the packet 
signature doesn’t match 
the packet contents. 
Check to find out where in the 
communications link noise or signal 
corruption is causing the data to be 
disrupted. 
Provider opened  The serial 
communications port has 
been initialized. 
 
Device dialed  The communications 
link has been initialized 
to transfer data packets. 
 
Provider closed  The serial 
communications port has 
been closed. 
 
Unable to Locate Serial synch 
byte  
 The low level 
communications 
synchronization byte was 
not received after the 
computer sent out a 
serial packet. 
This indicates that the device is 
either not responding or responding 
with an invalid communications 
protocol.  This message would 
appear if trying to talk to an array 
based datalogger that is set up as a 
table based datalogger in the 
network map. 
 
E-20