CG Drives & Automation, 01-5980-01r2 Functionality 85
Load Monitor Max Pre-Alarm autoreset
[2542]
The delay counter starts counting immediately.
Load Monitor Min Pre-Alarm autoreset
[2543]
The delay counter starts counting immediately.
Load Monitor Min Alarm autoreset
[2544]
The delay counter starts counting immediately.
External Alarm 1 autoreset [2549]
The delay counter starts counting as soon as the relevant
external alarm input is inactive.
External Alarm 2 autoreset [254A]
The delay counter starts counting as soon as the relevant
external alarm input is inactive.
Softstarter Protection autoreset [255]
For alarms that are present to protect the softstarter, the
following settings for autoreset can be done.
Overtemperature autoreset [2551]
In this menu the delay time for autoreset is set for a softstarter
overheated alarm. The delay time starts counting when the
fault is removed. This means the softstarter has to be cooled
down. When the delay time has elapsed, the alarm will be
reset.
Start Limitation autoreset [2552]
The delay counter starts counting when the time to next
allowed start, set in menu [2354], has decreased to zero.
Default: Off
Off 0 Off
1–3600 1–3600 1–3,600 s
Default: Off
Off 0 Off
1–3600 1–3600 1–3,600 s
Default: Off
Off 0 Off
1–3600 1–3600 1–3,600 s
Default: Off
Off 0 Off
1–3600 1–3600 1–3,600 s
Default: Off
Off 0 Off
1–3600 1–3600 1–3,600 s
Default: Off
Off 0 Off
1–3600 1–3600 1–3,600 s
Default: Off
Off 0 Off
1–3600 1–3600 1–3,600 s