Installing the 6200 network element 5-11
6200 Packet-Optical Platform Installation, Commissioning, and Testing Procedures
Release 1.1 009-6200-201 Draft Issue 1
Copyright
©
2014 Ciena
®
Corporation September 2014
Procedure 5-3
Connecting the DC power supplies
Use this procedure to connect the DC power supply to the base and
expansion chassis of the 6200 network element.
Prerequisites
Review the safety guidelines in Chapter 1, Observing product and personnel
safety guidelines.
• Make sure that the relevant circuit breaker is switched to OFF.
• Also make sure that the following tools and materials are available:
• standard installer tool kit
• four power cables per 6200 shelf (two for the base chassis and two for the
expansion chassis). Refer to the Planning Guide, S78-1002-110 for
ordering codes.
• miniature screwdriver
• digital multimeter
DANGER
Risk of electrocution
Working with live circuits is dangerous. Before you continue,
ensure that the rack power is turned off at the power
distribution panel and cannot be turned on accidentally. Use a
multimeter to verify that no potential exists.
CAUTION
Risk of equipment damage
Electrostatic discharge can damage electrostatic sensitive
devices. Use antistatic protection to avoid damaging the shelf
and circuit packs.