Loading...
Installing the 6200 network element 5-15
6200 Packet-Optical Platform Installation, Commissioning, and Testing Procedures
Release 1.1 009-6200-201 Draft Issue 1
Copyright
©
2014 Ciena
®
Corporation September 2014
Procedure 5-4
Connecting the AC power supply
Use this procedure to connect the AC Power supply to the base chassis of the
6200 network element.
Note 1: APU290 must be operated in redundant configuration only. A
combination of AC and DC power supply source is not supported on the
base chassis.
Note 2: When APU290 is present on the base chassis, a gap is left above
the power supply unit and slot 7 cannot be used. Hence, the unused slot
must be covered with an APU filler panel. Filler is used to arrest the
emission and dust. If the filler is not installed, dust can enter and block the
fan rotors.
Note 3: Use 3-pin AC power cord with Earth terminal connected to
building protective earth. AC power cords are country specific. Use an
appropriate power cord for installation.
Prerequisites
Review the safety guidelines in Chapter 1, Observing product and personnel
safety guidelines.
Make sure that the relevant circuit breaker is switched to OFF.
Also make sure that the following tools and materials are available:
standard installer tool kit
two power cables for the base chassis per 6200 shelf. Refer to the
Planning Guide, S78-1002-110 for ordering codes.
digital multimeter
DANGER
Risk of electrocution
Working with live circuits is dangerous. Before you continue,
ensure that the rack power is turned off at the power
distribution panel and cannot be turned on accidentally. Use a
multimeter to verify that no potential exists.
CAUTION
Risk of equipment damage
This equipment might have more than one power supply
connection. All connection must be removed to de-energize
the equipment. Always unplug the power cable before you
install or remove a power supply module of the system. Follow
the same procedure while installing or removing the system.