• DLP-G46 Log into CTC
• NTP-G37 Running Automatic Node Setup
Prerequisite Procedures
RequiredRequired/As Needed
Onsite or remoteOnsite/Remote
Superuser onlySecurity Level
Throughout this procedure, Side A refers to Slots 1 through 6, and Side B refers to Slots 12 through 17.
Note
Procedure
Step 1 Disable automatic laser shutdown (ALS) on Side A or (for terminal nodes) the terminal side OSCM or
OSC-CSM card:
a) In the node view (single-shelf mode) or shelf view (multishelf mode), double-click the Side A or
terminal-side OSCM or OSC-CSM card.
b) Click the Maintenance > ALS tabs.
c) From the ALS Mode drop-down list, choose Disable.
d) Click Apply. Click Yes in the confirmation dialog box.
Step 2 If an OSC-CSM or OSCM card is installed on Side B, complete the following steps. If not, continue with
Step 3.
a) In the node view (single-shelf mode) or shelf view (multishelf mode), double-click the Side B OSCM or
OSC-CSM card.
b) Click the Maintenance > ALS tabs.
c) From the ALS Mode drop-down list, choose Disable.
d) Click Apply. Click Yes in the confirmation dialog box.
Step 3 Complete the DLP-G314 Verifying OSCM Transmit Power, on page 62.
Step 4 Change ALS to Auto Restart on the Side A or (for terminal nodes) the terminal side OSCM or OSC-CSM
card:
a) In the node view (single-shelf mode) or shelf view (multishelf mode), double-click the Side A or
terminal-side OSCM or OSC-CSM card.
b) Click the Maintenance > ALS tabs.
c) From the ALS Mode drop-down list, choose Auto Restart.
d) Click Apply. Click Yes in the confirmation dialog box.
Step 5 If an OSC-CSM or OSCM card is installed on Side B, complete the following steps. If not, you have completed
this procedure.
a) In the node view (single-shelf mode) or shelf view (multishelf mode), double-click Side B OSCM or
OSC-CSM card.
b) Click the Maintenance > ALS tabs.
c) From the ALS Mode drop-down list, choose Auto Restart.
d) Click Apply. Click Yes in the confirmation dialog box.
Turning Up a Node
61
Turning Up a Node
NTP-G39 Verifying OSCM Transmit Power